Configure the Adapter with
Fixed IP Address
Configure the Adapter for Direct Connection in RSLogix 5000 Software
Notice the chassis size in the module is modified to 3.
9. Click OK.
At this point, your POINTBus status LED should be solid green. All
the yellow triangles in your I/O configuration should be gone.
To configure the 1734-AENT adapter with a fixed IP address to prevent the
adapter from ceasing to communicate with the ControlLogix controller:
1. Click the Port Configuration tab in the 1734-AENT adapter properties
dialog.
2. Uncheck the Enable DHCP box.
3. Click the Set button.
Publication 1734-UM011D-EN-P - May 2011
43