Rack Optimization; Add The Point I/O Module And Configure For Rack Optimization - Allen-Bradley Rockwell Automation 1734-AENT User Manual

Point i/o ethernet/ip adapter module
Hide thumbs Also See for Rockwell Automation 1734-AENT:
Table of Contents

Advertisement

Configure the Adapter for Direct Connection and Rack Optimization in RSLogix 5000 Software
The RPI is selectable, since it is a direct connection.
6. Verify that the requested packet interval (RPI) is appropriate for your
system (10 ms for this example). You use this value for the
rack-optimized connection to the I/O modules.
To avoid overloading the 1734-AENT adapter, we
IMPORTANT
recommend that the RPI be no less than 10 ms for rack
connections and 50 ms for direct connections.
7. Click OK to accept the configuration.
The 1734-AENT adapter appears indented under the local 1734-ENBT in
the I/O Configuration folder.

Add the POINT I/O Module and Configure For Rack Optimization

1. Right-click the 1734-AENT adapter under the I/O Configuration
folder, and select New Module.
If you exceed the 1734-AENT chassis size, trying to add
IMPORTANT
more modules than you configured, the New Module
selection appears dim and is disabled. Increase the
1734-AENT chassis size to add more POINT I/O
modules.
Publication 1734-UM011D-EN-P - May 2011
55