Digital 2 POINT Input

POINT I/O Module and RSLogix 5000 Software Controller Tag Reference
1734-IA2
2 POINT 120V AC Input
1734-IB2
2 POINT 10...28V DC Input, Sink
1734-IM2
2 POINT 240V AC Input
1734-IV2
2 POINT 10...28V DC Input, Source
Configuration Data
Filter Off On Time - POINT 0
Filter On Off Time - POINT 0
Filter Off On Time - POINT 1
Filter On Off Time - POINT 1
Input Data
Input Data - POINT 0, 1
Output Data
None
(1)
POINT I/O Modules support the Unsigned Integer data type UINT (0...65,535 range).
RSLogix 5000 software supports the signed Integer data type INT (-32,768 ...+32,767 range).
To enter Filter values from +32,768...+65,535 µs, use this conversion formula:
Desired Filter Value (in µs) - 65536 = Entered Filter Value (in µs).
As an example, for a 40 ms filter time, 40000 - 65536 = -25536
Data Type
Default
Valid Data Values
Value
INT
1,000
-32,768...32,767 µs
(0...65,535)
INT
1,000
-32,768...32,767 µs
(0...65,535)
INT
1,000
-32,768...32,767 µs
(0...65,535)
INT
1,000
-32,768...32,767 µs
(0...65,535)
Data Type
Default
Valid Data Values
Value
SINT, BIT
0
0=Off
1=On
Data Type
Default
Valid Data Values
Value
Publication 1734-UM011D-EN-P - May 2011
93
(1)
(1)
(1)