Configure the Adapter for Direct Connection and Rack Optimization in RSLogix 5000 Software
7. Verify that the requested packet interval (RPI) is appropriate for your
system.
You use this value for the rack-optimized connection to the I/O
modules.
To avoid overloading the 1734-AENT adapter, we
IMPORTANT
recommend that you set RPI no less than 10 ms for rack
connections and 50 ms for direct connections.
8. Click OK.
The 1734-AENT adapter appears in the Ethernet folder.
Add the POINT I/O Module and Configure for Direction
Connection
1. Highlight the 1734-AENT adapter under the I/O Configuration folder,
and select New Module.
The Select Module dialog opens.