58
Configure the Adapter for Direct Connection and Rack Optimization in RSLogix 5000 Software
Download the Program to
the Controller
Publication 1734-UM011D-EN-P - May 2011
The New Module Connection tab dialog opens.
8. On the Connection tab, enter 50 for the requested packet interval (RPI).
9. Keep the following unchecked:
• Inhibit Module
• Major Fault on Controller If Connection fails While in Run Mode
10. Click OK.
11. Choose File → Save and enter the name and location of the
RSLogix 5000 file.
Follow this procedure to download the program we just saved to the
ControlLogix controller.
1. From the main menu, choose Communications → Who-Active.
2. From the Who Active dialog, navigate to select the slot where the
controller is located in the chassis.