Adapter Web Pages
Work with the
Configuration Pages
Publication 1734-UM011D-EN-P - May 2011
3. From the Diagnostic Messaging tab, click Submit to see values similar to
that in the figure.
To work with the Configuration pages, follow these procedures, noting that
values on these pages are stored in and retrieved from non-volatile memory.
The values on these pages are in non-volatile memory.
IMPORTANT
Changes to these parameters do not take effect until you
reset or cycle power to the 1734-AENT adapter.
If you set the thumbwheels on the 1734-AENT adapter to
IMPORTANT
the value 888 and then power cycle the module, the
following occurs:
• The DHCP Enabled function is enabled (set to True).
• The Ethernet link is negotiated automatically. The Auto
Negotiate function is set to True.
• The Web server is enabled. The Disabled Web Server
function is disabled.
• The password for this page resets to the factory default.
The word password is the factory default password.
Note the value of the switches before you enter the 888
value because you return the adapter to those values once
this process is complete.
1. From the Home page, click Configuration or Expand to see the
Configuration options, if needed.