POINT I/O Module and RSLogix 5000 Software Controller Tag Reference
Digital 2 POINT Output –
With Over Load and Open

Load Diagnostic Status

Publication 1734-UM011D-EN-P - May 2011
1734-OB2E
2 POINT 10...28V DC Electronically Fused Output, Source
1734-OB2EP
2 POINT 10...28V DC Electronically Fused Protected Output, Source
Configuration Data
Fault Mode - POINT 0, 1
Fault Value - POINT 0, 1
Program Mode - POINT 0, 1
Program Value - POINT 0, 1
No Load Enable - POINT 0, 1
(Wire Off Diagnostic)
Auto Restart Enable - POINT 0, 1
(Over Load Behavior)
Fault Latch Enable - POINT 0, 1
(Open Load or Over Load)
Input Data
Status Data - POINT 0, 1
(Open Load or Over Load)
Output Data
Output Data - POINT 0, 1
Data Type
Default
Valid Data Values
Value
SINT, BIT
0
0=Fault Value
1=Hold Last State
SINT, BIT
0
0=Off
1=On
SINT, BIT
0
0=Program Value
1=Hold Last State
SINT, BIT
0
0=Off
1=On
SINT, BIT
1
0=Disabled
1=Enabled
SINT, BIT
0
0=Latch Off
1=Auto Retry
0=No Latching
SINT, BIT
0
1=Alarms Latch
Data Type
Default
Valid Data Values
Value
SINT, BIT
0
0=Off
1=On (Load Fault)
Data Type
Default
Valid Data Values
Value
SINT, BIT
0
0=Off
1=On