What This Chapter Contains

63
LED Status Indicators
Read this chapter for information about LED status indicators.

Interpret the Status Indicators

You must use series C POINT I/O modules with the
ATTENTION
1734-AENT adapter. Series A or B POINT I/O modules will
not work with this adapter.
Indication
Probable Cause
Module Status
Off
No power applied to device
Flashing
LED cycle power test (module
red/green
self-test) present.
Solid green
Device is operating normally.
Flashing red
Recoverable fault has occurred:
Firmware (NVS) update present.
Address switches changed.
Solid red
Unrecoverable fault has occurred:
Self-test failure present
(checksum failure, or RAMtest
failure at cycle power).
Firmware fatal error present.
Module Status
Network Activity
Network Status
POINTBus Status
System Power
Field Power
43248aent
Recommended Action
Apply power to the device.
None
None
Complete firmware update.
Verify address switches.
Replace adapter.
Publication 1734-UM011D-EN-P - May 2011