Set the DeviceNet Node
Address and Baud Rate
Set the Linking Device
IP Address
Two methods can be used to set the DeviceNet node address and the baud rate:
• Use the node address and baud rate rotary switches on the linking device
• Use RSNetWorx for DeviceNet software
Set the DeviceNet Node Address and Baud Rate by Using the

Rotary Switches

Set the desired node address and baud rate using the rotary switches on the
device, according to these tables.
Set the DeviceNet Node Address and Baud Rate by Using RSNetWorx
for DeviceNet Software
See
Set the DeviceNet Node Address and Baud Rate on page 46
about using RSNetWorx software to set node address and baud rate.
Four methods can be used to set the linking device IP address:
• Use the IP address rotary switches on the linking device
• Use the DHCP protocol
• Use RSLinx software
• Use the web pages of the linking device
Rockwell Automation Publication 1788-UM059B-EN-P - September 2015
Install the 1788-EN2DNROM Linking Device
Switch
Node Address
00 - 63
DeviceNet node address
Other value Node address selected via RSNetWorx
software
Switch
Baud Rate
0
125 kbps
1
250 kbps
2
500 kbps
Other value Baud rate selected via RSNetWorx
software
Chapter 2
for information
19