SensyMaster FMT430, FMT450 THERMAL MASS FLOWMETER | OI/FMT430/450-EN REV. B
Configuring the digital outputs
Easy Setup
Dig.Out 41/42 Mode
Off
Next
16. Use
to call up the edit mode.
17. Use
/
to select the desired operating modeOff,
Binary, Pulse, Frequencyfor the digital output.
18. Confirm the selection with
Easy Setup
Freq.Out 41/42
Mass Flow [%]
Next
19. Use
to call up the edit mode.
20. Using
/
, select the desired process value for
frequency output 41 / 42.
21. Confirm the selection with
Easy Setup
Freq.Out 41/42 100%
10000 Hz
Next
22. Use
to call up the edit mode.
23. Using
/
set the frequency for 100 % of the flow rate.
24. Confirm the selection with
Easy Setup
Freq.Out 41/42 0%
0 Hz
Next
25. Use
to call up the edit mode.
26. Using
/
set the frequency for 0 % of the flow rate.
27. Confirm the selection with
Edit
.
Only available if "Dig.Out 41/42 Mode"
Frequency has been selected.
Edit
.
Only available if "Dig.Out 41/42 Mode"
Frequency has been selected.
Edit
.
Only available if "Dig.Out 41/42 Mode"
Frequency has been selected.
Edit
.
Easy Setup
Puls.Out 41/42
Mass Flow [%]
Next
28. Use
to call up the edit mode.
29. Using
/
, select the desired process value for pulse
output 41 / 42.
30. Confirm the selection with
Easy Setup
Puls.Out 41/42 Width
30.00 ms
Next
31. Use
to call up the edit mode.
32. Use
/
to select the desired pulse width for the pulse
output..
33. Confirm the selection with
Easy Setup
Dig.Out 41/42
Alarm
Next
34. Use
to call up the edit mode.
35. Using
/
, select the desired function for binary output
41 / 42.
36. Confirm the selection with
Easy Setup
Dig.Out 51/52 Mode
Off
Next
37. Use
to call up the edit mode.
38. Use
/
to select the desired operating modeOff,
Binary, Frequency, Pulse 41/42 <)90°, Pulse 41/42 <)180°for
the digital output.
39. Confirm the selection with
Only available if "Dig.Out 41/42 Mode"
Pulse has been selected.
Edit
.
Only available if "Dig.Out 41/42 Mode"
Pulse has been selected.
Edit
.
Only available if "Dig.Out 41/42 Mode"
Binary has been selected.
Edit
.
Edit
.
77