110
SensyMaster FMT430, FMT450 THERMAL MASS FLOWMETER | OI/FMT430/450-EN REV. B
... 9 Operation
... Parameter descriptions
Menu / parameter
Device Setup / ...Transmitter / ...Units
Variable 1 Name
Variable 2 Name
Device Setup / ...Transmitter / ...Custom Units
Mass flow Qm Name
Mass flow Qm Factor
Mass Tot. Name
Mass Tot. Factor
Volumeflow Qv@ Name
Volumeflow Qv@ Fact.
Volume@ Tot. Name
Volume@ Tot. Factor
Density@ Name
Density@ Factor
Device Setup / ...Transmitter / ...Feature Settings
FillMass On/Off
FillMass Code
VeriMass On/Off
VeriMass Code
Description
Selection of the unit for external process variables.
The transmitter can show two external process variables in the display. The process variables can be transferred from a
fieldbus master to the transmitter via the HART®, Modbus® oder PROFIBUS DP® protocol. You can configure the indicator
through the 'Display' menu.
Enter the name of the user-defined unit for mass flow.
Alphanumeric, maximum 7 characters.
Enter the factor for the user-defined unit for mass flow.
Setting range: 0.0001 ... 100000 kg/h
Enter the name of the user-defined totalizer unit for mass flow.
Alphanumeric, maximum 7 characters.
Enter the factor for a user-defined totalizer unit.
Setting range: 0.0001 ... 100000 kg
Enter the name of the user-defined unit for standard volume flow.
Alphanumeric, maximum 7 characters.
Enter the factor for the user-defined unit for standard volume flow.
Setting range: 0.0001 ... 100000 m
Enter the name of the user-defined totalizer unit for standard volume flow.
Alphanumeric, maximum 7 characters.
Enter the factor for the user-defined totalizer unit for standard volume flow.
Setting range: 0.0001 ... 100000 m
Enter the name of the user-defined unit for standard density.
If the first character is a space, a @ sign will be appended to the unit (standard setting).
Alphanumeric, maximum 7 characters.
Enter the factor for a user-defined standard density.
Setting range 0.0001 ... 100000 kg/m
FillMass function active?
Off:
FillMass function deactivated.
On:
FillMass function activated.
Sets the device-specific code for activating the FillMass function. To use this function subsequently, contact the ABB
service team or sales organization.
After entering the code, restart the device (by for example using the parameter 'Perform Device Reset', or by briefly
switching off the power supply).
VeriMass function active?
Off:
VeriMass function deactivated.
On:
VeriMass function activated.
Sets the device-specific code for activating the FillMass function. To use this function subsequently, contact the ABB
service team or sales organization.
After entering the code, restart the device (by for example using the parameter 'Perform Device Reset', or by briefly
switching off the power supply).
3
/hour in standard conditions.
3
in standard conditions.
3

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sensymaster fmt450