116
SensyMaster FMT430, FMT450 THERMAL MASS FLOWMETER | OI/FMT430/450-EN REV. B
... 9 Operation
... Parameter descriptions
Menu / parameter
Input/Output / ...Dig.Out 51/52 / ...Puls.Out 51/52
Signal Source Pulse
Quantity Pulses
Quantity Mass
Quantity Volume@
Pulse Width
Input/Output / ...Dig.Out 51/52 / ...Freq.Out 51/52
Signal Source Freq.
Upper Range Value
Lower Range Value
Input/Output / ...Dig.Out 51/52 / ...Binary Out 51/52
Signal Source Binary
Active Mode
Input/Output / ...Dig.Out 51/52 / ...Alarm Cfg. 51/52
General Alarm
Qm Massflow Max
Qm Massflow Min
Qv@ Volumeflow Max
Qv@ Volumeflow Min
Tm Temperature Max
Tm Temperature Min
Sensor Soiling
Description
Display of parameters that have been set in the '...Puls.Out 41/42' menu.
Selection of process variable that is issued via the frequency output.
Refer to Available process variables on page 98.
Set the frequency range for output of the selected process variables.
•
Upper Range Value: Set the frequency for 100 % of the process variable.
•
Lower Range Value: Set the frequency for 0 % of the process variable.
Selection of binary output function.
•
Alarm: The binary output indicates an active alarm. The alarm is selected in the '„...Alarm Cfg. 51/52' menu.
•
Batch End: The binary output is activated when the set fill quantity is reached (only if the FillMass function is activated).
Select switching properties for the binary output.
•
Active High: Normally open
•
Active Low: Normally closed
Selection of error messages signaled via the binary output 51 / 52.
Only if the parameter "Signal Source Binary" has been set to "Alarm".
In preparation