ABB SensyMaster FMT430 Operating Instructions Manual page 132

Thermal mass flowmeter
Table of Contents

Advertisement

132
SensyMaster FMT430, FMT450 THERMAL MASS FLOWMETER | OI/FMT430/450-EN REV. B
... 10 Diagnosis / error messages
... Error messages
Error number
Error text
C078.003
Flowrate to zero
C076.005
All totalizer stopp.
C074.006
Totalizer reset. Reset of one
or more Totalizers.
C072.002
Simulation is on! Simulating
process/output value
C070.026
An alarm is simulated.
S090.031
Sensor temperature out of
range.
S065.028
CO31/32 readbackcurrent
deviates
S055.032
Frontend temp. out of range. Device temperature outside of permissible limit values.
S052.016
Curr.Out 31/32 is saturated. Current output 31 / 32 overshot. The flow has exceeded the set upper measuring range
S051.017
Curr.Out V1/V2, V3/V4
saturated
S049.019
Option Card 1 com error.
S048.020
Option Card 2 com error.
S047.015
Dig.Out 41/42 is saturated.
S046.042
Dig.Out 51/52 is saturated.
Description
External switch-off active via digital input.
Check status of digital input.
Check parameterization.
External totalizer switch-off active via digital input.
Check status of digital input.
Check parameterization.
Reset of one or more counters.
Check status of digital input.
Check parameterization.
Simulation mode is active.
Deactivate simulation mode in the 'Diagnostics / ......Simulation Mode' menu.
The alarm simulation is active.
Deactivate alarm simulation in the 'Diagnostics / ...Alarm Simulation' menu.
The temperature of the thermal measuring element is outside the permissible limits.
Measuring medium temperature outside of the set alarm threshold or permissible limit
values.
Check parameterization, see menu Menu: Process Alarm on page 118
Check process conditions, see chapter Process conditions on page 30
Current loop error current output 31 / 32.
Check current loop current output 31 / 32 (short-circuit / interruption).
Check load current output 31 / 32.
Check the power supply (voltage) of the transmitter.
Check ambient temperature (see Ambient conditions on page 27)
value.
Check the upper range value Qv@ Max, Qm Max in the 'Device Setup / ...Sensor' menu
and correct if necessary.
Current output V1 / V2, V3 / V4 (plug-in card) overshot. The flow has exceeded the set upper
measuring range value.
Check the upper range value Qv@ Max, Qm Max in the 'Device Setup / ...Sensor' menu
and correct if necessary.
Communication error to plug-in card.
Check that the plug-in card is installed correctly.
Replace plug-in card if necessary.
Contact ABB Service.
The pulse rate or the frequency at the pulse output 41 / 42 is outside the permissible limits.
Check configuration of the parameters for the pulse output.
The pulse rate or the frequency at the pulse output 51 / 52 is outside the permissible limits.
Check configuration of the parameters for the pulse output.
NAMUR
classification
Functional check
Functional check
Functional check
Functional check
Functional check
Out of specification
Out of specification
Out of specification
Out of specification
Out of specification
Out of specification
Out of specification
Out of specification