SensyMaster FMT430, FMT450 THERMAL MASS FLOWMETER | OI/FMT430/450-EN REV. B
Menu / parameter
Input/Output / ...Dig.Out 41/42 / ...Binary Out 41/42
Signal Source Binary
Active Mode
Input/Output / ...Dig.Out 41/42 / ...Alarm Cfg. 41/42
General Alarm
Qm Massflow Max
Qm Massflow Min
Qv@ Volumeflow Max
Qv@ Volumeflow Min
Tm Temperature Max
Tm Temperature Min
Sensor Soiling
Input/Output / ...Dig.Out 51/52
Mode
...Puls.Out 51/52
...Freq.Out 51/52
...Binary Out 51/52
...Alarm Cfg. 51/52
Description
Selection of binary output function.
Alarm: The binary output indicates an active alarm. The alarm is selected in the '„...Alarm Cfg. 41/42' menu.
Batch End: The binary output is activated when the set fill quantity is reached (only if the FillMass function is activated).
Select switching properties for the binary output.
Active High: Normally open
Active Low: Normally closed
Selection of error messages signaled via the binary output 41 / 42.
Only if the parameter "Signal Source Binary" has been set to "Alarm".
In preparation
Selection of the operating mode for the digital output 51 / 52. The following operating mode Pulse 41/42 <)90°, Pulse 41/42
<)180°" is only available if the digital output 41 / 42 has been configured as a pulse output.
Off: Digital output deactivated.
Binary: Digital output configured as a binary output (for function see parameter '...Binary Out 51/52').
Frequency: Digital output 51 / 52 as a frequency output. In frequency mode, a frequency is issued that is proportional to
the flow rate.
Pulse 41/42 <)90°: Output of the same pulses as for digital output 41 / 42, phase shifted by 90°.
Pulse 41/42 <)180°: Output of the same pulses as for digital output 41 / 42, phase shifted by 180°
Selection of submenu '...Puls.Out 51/52' using
Selection of submenu '...Freq.Out 51/52' using
Only available if 'Mode' Frequency has been selected.
Selection of submenu '...Binary Out 51/52' using
Only available if 'Mode' Binary has been selected.
Selection of submenu '...Alarm Cfg. 51/52' using
Only available if 'Mode' Binary has been selected.
.
.
.
.
115