4.2.3
Data Logger Configuration
For the convenience of recording acquisition tag's historical data, iRTU Studio provides data
logger configuration function. Users can select the acquisition tag, recording period (seconds)
and maximum recording days (day) according to the requirements. The historical data of each
day is stored in a file, which is stored in a SD card. iRTU Studio can calculate the occupied
memory in SD card of the historical data according to the recording period and recording
days. Pay attention to the total memory of SD card, which must be bigger to the calculated
memory. The specific parameter setting is as follows:
Recording acquisition tag: the maximum is 200 tags.
Recording period (second): Positive integer value.
Recording maximum days (day): Integer value between 0~99.
In order to directly read the field data or prevent data loss caused by the communication insta-
bility, users can enable the USB backup function. In this way, users can directly insert the
USB into the ADAM-3600-C2G to copy the historical data in SD card. PROM indicator will
always be blinking until finishing the process of copying. The historical data is stored in the
form of SQLite. If users want to read the file, please contact Advantech customer service. We
will help you to read the data.
4.2.4
Protocol Service Configuration
The ADAM-3600-C2G is an open basis intelligent RTU which is able to integrate many kinds
of communication protocol to communicate with the center station. And it is default with two
standard protocol services: Modbus and DNP3.
4.2.4.1
Modbus Service
The ADAM-3600-C2G can be used as Modbus Server for Modbus Client accessing. There
are two types of services supported: Modbus TCP Server and Modbus RTU Server
Users can check the Checkbox to enable the services, fill all the required parameters for
these services and click "Apply".
Note if all the serial ports are occupied there will pop-up and error message while you enable
the Modbus RTU Server. Go back to "Data Center" tree-view to release COM port resource.
To release the COM port, right click on the resource and select "Delete", the resource will be
remove from the "Data Center" configuration.
ADAM-3600-C2G Modbus address mapping: Modbus Client request data of Server by Mod-
bus addressing. Thus, in the lower table is an interface to map the tags with Modbus address.
To add tag into Modbus address list, please double click the field of column "Tag Name" and
select the tag from the tree-view as shown on below figure. And select the "Tag Type" from
the draw down list. If the tag is an analogue type (AI/AO), please also select the related "Data
Type" from the draw down list.
ADAM-3600 Series User Manual
Figure 4.20 Historical recording data configuration
34