4.2. Control Panel

Main LED (green)
On
Light on (100ms ON every 4s)
Flashing slow (0.5s ON, 1.5s OFF)
Flashing fast (250ms ON, 250ms OFF)
Stopping
Battery LED (green)
On
Flashing fast (250ms ON, 250ms OFF)
Stopping
Security LEDs
(green, amber, red)
One of them is on
Flashing amber LED (500ms ON, 1.5s OFF) End of discharge log indicator. Eliminated on
Alternate green and red LED (250ms each
LED)
Flashing red LED (500ms ON, 1.5s OFF)
LPS24 – USER MANUAL
Presence of network and without test.
Remote network failure (with network at the
unit's input).
Network is present and is performing a duration
test or a capacity test.
Network is present and is performing a functional
test.
Network failure on the unit's input.
Battery correct.
In network malfunction an upcoming end of
discharge is estimated (remaining duration less
than 10 mins.).
Occurs in any of the following situations:
- Battery open or in bad state
- Incorrectly connected battery
- Battery voltage equal or less than end of
discharge voltage
- Battery voltage very high
- Battery fuse open
- Battery contactor open
Equipment safety level:
-Green: installation secure
-Amber: installation with maintenance warning
-Red: installation not secure
confirming that the notification has been read.
Bootloader start up, waiting for activation
sequence.
Zoning in progress.