#Start zoning:
enables the luminaires to be divided by zone without manually placing
them in a circuit. Only available for connected luminaires that are unplaced.
Regardless of how the luminaire's operating mode is configured, once
it has started, if the status of the power-lum input is modified, the
on/off status of the luminaire's light source will attend to this order.
There is a circuit called "unlocated" corresponding to the luminaires with a position that is
not known in the device. There may be two reasons. The device has been connected to
the unit and has not performed zoning (see 7.2.2) or the
circuit configured with a type other than "ELC". In a perfectly configured device, there
should be no luminaire associated with that circuit.

8.2.5. Actions

8.2.5.1. Actions
This screen shows the various actions that can be run on the device. Depending on the
unit's status, the options available are displayed.
Overview
OK Main menu
Start/cancel fast charge:
Battery charge 100%:
estimate to 100%.
Uninstall lumin:
if there is any uninstallable luminaire (to be uninstallable it must have
a communication fault with the device), it can be de-registered from the device. Use the
keys (< and >) to go through the serial numbers of the uninstallable luminaires.
Start zoning:
runs a zoning process on the luminaires (see section 12.1.2). Only
displayed if the safety conditions necessary for zoning the device are given.
Rectifier test:
test the rectifier to correct its fault. Only displayed if the device has
detected a fault in the rectifier.
Activate rest mode:
of power failure on the device.
Exec circuit test:
runs a circuit test (see section 12.1.1). Only displayed if the safety
conditions necessary for testing the circuits are given.
Stop buzzer:
stops the audible alarm for 30 minutes to be able to operate with a faulty
device more comfortably.
LPS24 – USER MANUAL
>
ACTIONS
#Start fast charge
#Battery charge 100%
#Uninstall lumin.
#Start zoning
#Rectifier test
#Activate rest mode
#Exec circuit test
# Stop buzzer
Actions
start a fast battery charge or end early if it is running.
send a command to the device to place the battery charge
places the device and luminaires in standby. Only available in case
www.daisalux.com
ELC
luminaire is connected to a
Actions
OK
280542
Scenes
31