10.3.2. ELC luminaires not installed:

• If after connecting ELC series luminaires it is observed that they are not installed on
the device, review the following points:
The circuits must be configured in "ELC" mode
The device's communication is only possible with Daisalux ELC series 24v luminaires.
Communication with new luminaires connected to the device can take up to 60
minutes to establish from when they are connected to the device.
If the luminaires have been previously connected to another device, they must
remain connected and with power for 24 hours to the new device so that they are
installed on it.
The distance from the device to the first luminaire on the circuit and between
luminaires on the same circuit must not exceed 80 metres. At greater distances,
correct communication of luminaires with the device is not guaranteed.
Check that the luminaires have power on their terminals. Check wiring on the circuit if
there is no voltage on its input.
If there is input voltage, check that the light or one of the light's signalling LEDs is
illuminated or flashing. Otherwise, check the connection to the luminaire's terminals
or between the anchor plate and the luminaire.

10.4. Battery Problems:

10.4.1. Battery duration fault:

When the device notifies a duration fault, check the following:
• Device's output power (must be within the ranges described in this manual). If the
power is excessive it is outside of specifications and therefore its duration is reduced
to below that configured.
• If the power is within range, the battery will probably have to be replaced with a new
one.

10.4.2. Reversed battery connection:

If there is a reversed battery connected, the fuses must be replaced after disconnecting
the battery. After replacing the fuses, reconnect the battery according to the polarity
indicated.

11. Accessories

11.1 LPSLan/LPSWeb/ModBus

LPSLan is an accessory that adds ethernet connectivity to LPS24 devices. It includes a web
server (LPSWeb) used to configure and display the status of centralised LPS series Daisalux
through a local or internet network. The system includes a
the LPS24 equipment. See connection information in
It can accessed from a web browser so there is no need to install any additional software on
your computer, tablet or smartphone. The only requirement is that you have a web browser
and a network connection with the LPS series device.
From the LPSWeb the device status can be viewed and certain aspects of its operation
configured, as well as the centralised luminaires on the Daisalux ELC series connected to it.
For a detailed description of the operating mode, consult the
LPS24 – USER MANUAL
6.3.7 LPSLan
www.daisalux.com
ModBus
gateway for managing
LPSWeb
manual.
37