Appendix; Alert Messages - daisalux LPS24 Series User Manual

Centralised emergency lighting device
Hide thumbs Also See for LPS24 Series:
Table of Contents

Advertisement

8.2.7. Appendix

8.2.7.1. Alert messages

When the device detects an alert, a pop-up is generated on the display with the error
message. The user can remove the pop-up by pressing the OK or ← key.
Below is a list of the alerts available and an explanation.
Alert
End of bat discharge log
Battery is running down
Input overvoltage
System overload
Mains failure
Remote mains failure
Global siwtch on active
DBR switch on active
Internal voltage error
Battery voltage error
Wrong battery temperature
Function test on course
Duration test on course
Capacity test on course
Circuit test on course
Duration test required
Function test failure
Duration test severe fail
Duration test light fail
Battery bad connected
Battery open
Battery not symmetric
Battery fuse failure
Temperature sensor failure
Output circuit failure
Battery charge failure
Rectifier failure
Electronic failure
Contactor open
Zoning on course
Shutting down ...
Command executed
Password: 0000
Low security
Very low security
LPS24 – USER MANUAL
A record indicating that the device has been in standby since reaching
the end of discharge
The device detects that it has energy for less than 10 minutes
The device has detected a voltage on the input well above its nominal
voltage
The device has detected that the load connected is higher than its
maximum power
Mains failure on the unit's input.
Mains failure in a remote mains detector associated with the device
Active auxiliary switch on
Active DBR switch on
Voltage generated by the rectifier outside of range
Battery voltage out of range
Temperature in the battery compartment outside of range
The device is running a functional test
The device is running a duration test
The device is running a capacity test
The device is running a circuit test
The duration test period has transpired without a test having been
performed. A test must be run to check the system's duration
Fault detected in the last functional test
A serious fault was detected during the last duration test (duration less
than 60% of the nominal duration)
A minor fault was detected during the last duration test (duration higher
than 60% and lower than 100% of the nominal duration)
Incorrectly connected battery
Battery open or in bad state
Batteries not symmetrical. Possible fault in a battery
Fault in any of the battery fuses
Failure in the communication with the temperature probe
A circuit fault
Battery charge regulation fault
Failure in the rectifier
Fault in the device's electronics. Requires repair
Contactor open. Installation uncertain in the event of power failure.
The device is running a zoning process
The device is in standby
User command executed
Request the password required to edit the value or execute the order
The device estimates that the installation requires maintenance
The device estimates that the installation is unsafe
www.daisalux.com