6.3.3.2 Remote fault connection to several LPS24 devices

Another possible configuration would be that of several remote faults associated with an
LPS system, which through a dry output pre-configured into the next device in the
auxiliary input, this in turn would pass to the next LPS system, thus a remote fault would
be associated in series to several LPS systems.
The optional contact-free potential must be programmed according to the instruction, see
8.2.3.2. Relay configuration.
6.3.4. Dry contacts (CLP1, ..., CLP4)
There are four dry contacts, three of them fixed according to the EN 50171 standard and
the fourth configurable by the user.
Available options
System working
Mains failure
Local mains failure
Communicated with a
PC
Global switch on active
DBR switch on active
Zoning on course
Battery is running
down
Contactor open
LPS24 – USER MANUAL
Option details
• System in operation (not in standby)
• Mains failure on the unit's input
• Remote mains failure (not on the unit's
input)
• System with active communication with a
PC (Daisatest, WinCB or access to web
server)
• Device with active auxiliary switched on
• Device with active DBR switched on
• Device running luminaire zoning
• Alarm for next end of active discharge
• Battery contactor open
www.daisalux.com
Default configuration of
the contacts
1
2
3
4
Buzzer