Electrical Connections; Power Connection; Output Circuits (Out1 - daisalux LPS24 Series User Manual

Centralised emergency lighting device
Hide thumbs Also See for LPS24 Series:
Table of Contents

Advertisement

6.3. Electrical connections

The wiring of the LPS centralised power unit is on the top of the same.

6.3.1. Power connection

Connect the power supply to terminals L, N and earth (PE).
6.3.2.Output circuits (OUT1, ..., OUT6)
The LPS system has six output circuits for monitoring the luminaires
(ELC, "beacons",
non-communicating). These outputs must be pre-
configured, see
8.2.4. Configuring the outputs
Each circuit supports a maximum output of 4 A of constant current
with intelligent protection against over-consumption and/or short
circuit. Caution: check that the total load does not exceed the system
output power. See
5. Technical
Check the compatibility of each luminaire connected to an
!
output circuit configured as "beacons", as not all beacons allow
such functionality.
The ELC luminaires are not compatible with outlets configured
!
as "beacon".
On the outputs defined as beacons, it is recommended not to adjust
!
the load over 3A (75% of the maximum 4A) to avoid possible over-
consumption on tests.
If low voltage (MBTS) is used to wire the luminaires there is no need for protection by
ground wire cable (PE). Observe the maximum lengths depending on the cable section
specified in
A. Cable length
The luminaires are connected to the + and - terminals, which are duplicated in the
centralised power unit; i.e. it has two outputs for each circuit. To configure the luminaires
see
8.2.4.2. Luminaires
LPS24 – USER MANUAL
data.
www.daisalux.com
13

Advertisement

Table of Contents
loading

This manual is also suitable for:

Lps24-26Lps24-65

Table of Contents