4 .6 LCD Setting

Press and hold the select button for 5 seconds to enter the UPS setting mode when the UPS is in
the standby mode or the bypass mode. Press and hold "Off/Enter" and the "select" buttons for
five seconds to switch the LCD screen in the Rack or Tower display.
Rack Display
There are two parameters to set up the UPS.
Parameter 1: This is for program alternatives. Refer to the table below.
Parameter 2: The setting options or values for each program.
01: Output voltage setting
Interface
02: Frequency converter enable/disable
Interface
03: Output frequency setting
Interface
Parameter 2
Parameter 1
Setting
Parameter 2: Output voltage
For 100/110/115/120/125 VAC models, you may choose the following output voltage:
100: presents output voltage as 100Vac
110: presents output voltage as 110Vac
115: presents output voltage as 115Vac
120: presents output voltage as 120Vac (Default)
125: presents output voltage as 125Vac
Setting
Parameter 2: Enable or disable the converter mode. You may choose the following
two options:
CF ENA: converter mode enable
CF DIS: converter mode disable (Default)
Setting
Parameter 2 : Output frequency setting.
You may set the initial frequency on the battery mode:
50: output frequency is 50Hz
60: output frequency is 60Hz
If the converter mode is enabled, you may choose the following output frequency:
50: output frequency is 50Hz
60: output frequency is 60Hz
Tower Display
Parameter 2
Parameter 1