4 Operation

This chapter describes how the UPS is operated through the
LCD.
The user can:
• Operate the LCD
• Start up and shut down the UPS (excluding the
commissioning start up)
• Operate additional SNMP adapters and their software

4 .1 Control panel

4.1-1:
Control panel
LCD
Selection
keys
4.1-1
4 .1 .1
Table 3: UPS selection keys
Button

Selection keys

Function
Illustration
• Turn on the UPS: Press and the hold ON/Mute button for at least 2 seconds to turn on the UPS.
• Mute the alarm: After the UPS is turned on in battery mode, press and hold this button for at least 3 seconds to
ON/Mute
disable or enable the alarm system. But this is not applied to those situations when warnings or errors occur.
Button
• Up key: Press this button to display the previous selection in the UPS setting mode.
• Switch to UPS self-test mode: Press the ON/Mute buttons for 3 seconds to enter UPS self-testing while in AC mode,
ECO mode, or converter mode.
• Turn off the UPS: Press and hold this button for at least 2 seconds to turn off the UPS. The UPS will be in standby
OFF/Enter
mode under power normal or transfer to Bypass mode if the Bypass enables the setting by pressing this button.
Button
• Confirm selection key: Press this button to confirm the selection in the UPS setting mode.
• Switch LCD message: Press this button to change the LCD message for input voltage, input frequency, battery
Select
voltage, battery current, battery capacity, output voltage, output frequency, load current and load percent.
Button
• Setting mode: Press and hold this button for 3 seconds to enter UPS setting mode when in Standby and Bypass mode.
• Down key: Press this button to display the next selection in the UPS setting mode.
• Switch to bypass mode: When the main power is normal, press the ON/Mute and Select buttons simultaneously for
3 seconds. Then the UPS will enter bypass mode. This action will be ineffective when the input voltage is out of
ON/Mute +
acceptable range.
Select Button
• Exit setting mode or return to the upper menu: When working in setting mode, press the ON/Mute and Select
buttons simultaneously for 0.2 seconds to return to the upper menu. If this is already in top menu, press these two
buttons at the same time to exit the setting mode.
OFF/Enter +
• Rack or Tower display switch: Press the Select and OFF/Enter buttons simultaneously for 3 seconds.
Select Button
The display changes from/to Rack to/from Tower.
The user-friendly control panel has two parts:
• Selection keys
• Power management LCD (PMD)