4 O P E R AT I O N
04: ECO enable/disable
Interface
05: ECO voltage range setting
Interface
06: Bypass enable/disable when UPS is off
Interface
Setting
Parameter 2: Enable or disable the ECO function. You may choose the following
two options:
ENA: ECO mode enable
DIS: ECO mode disable (Default)
Setting
Parameter 2: Set the acceptable high voltage point and low voltage point for the ECO
mode by pressing the Down key or Up key.
HLS: High loss voltage in ECO mode in parameter 2.
For 100/110/115/120/125 VAC models, the setting range is from +3V to +12V of the
nominal voltage. (Default: +6V)
LLS: Low loss voltage in ECO mode in parameter 2.
For 100/110/115/120/125 VAC models, the setting voltage is from -3V to -12V of the
nominal voltage. (Default: -6V)
Setting
Parameter 2: Enable or disable the Bypass function. You may choose the following two
options:
ENA: Bypass enable
DIS: Bypass disable (Default)
23