4 O P E R AT I O N
11: Autonomy limitation setting
Interface
12: Battery pack number setting
Interface
13: Charger Boost voltage setting
Interface
14: Charger Float voltage setting
Interface
15: EPO logic setting
Interface
Setting
Parameter 2: Set up the backup time on the battery mode for general outlets.
0-999: setting the backup time in minutes from 0-999 for general outlets on
the battery mode.
DIS: Disable the autonomy limitation and the backup time will depend on battery
capacity. (Default)
Note: When setting as "0", the backup time will be only 10 seconds.
Setting
Parameter 2: Set up the Battery pack number.
0-6: setting up the external battery package number from 0-6. (Default: 0)
Note: Automatically adjust the charging current with the battery pack quantity.
EBM number
0
1
2-6EBM
Setting
Parameter 2: Set up the charger boost voltage.
2.25-2.40: setting the charger boost voltage from 2.25 V/cell to 2.40V/cell.
(Default: 2.36V/cell)
Setting
Parameter 2: Set up the charger float voltage.
2.20-2.33: setting the charger float voltage from 2.20 V/cell to 2.33V/cell.
(Default: 2.28V/cell)
Setting
Parameter 2: Set up the EPO function control logic.
AO: Active Open (Default). When AO is selected as EPO logic, it will activate the EPO
function with Pin 1 and Pin 2 in open status.
AC: Active Close. When AC is selected as EPO logic, it will activate the EPO function with
Pin 1 and Pin 2 in close status.
Charging current (A)
2
4
6
25