A B B U P S P R O D U C T S A N D S O L U T I O N S
07: Bypass voltage range setting
Interface
08: Bypass frequency range setting
Interface
09: Programmable outlets enable/disable
Interface
10: Programmable outlets setting
Interface
Setting
Parameter 2: Set the acceptable high voltage point and acceptable low voltage point for
the Bypass mode by pressing the Down key or the Up key.
HLS: Bypass high voltage point
For 100/110/115/120/125 VAC models:
120-140: setting the high voltage point from 120Vac to 140Vac.
(Default: 132Vac)
LLS: Bypass low voltage point
For 100/110/115/120/125 VAC models:
85-115: setting the low voltage point from 85Vac to 115Vac.
(Default: 85Vac)
Setting
Parameter 2: Set the acceptable high frequency point and acceptable low frequency
point for the Bypass mode by pressing the Down key or the Up key.
HLS: Bypass high frequency point
For 50Hz output frequency models:
51-55Hz: setting the frequency high loss point from 51Hz to 55HZ(Default: 53.0Hz)
For 60Hz output frequency models:
61-65Hz: setting the frequency high loss point from 61Hz to 65Hz(Default: 63.0Hz)
LLS: Bypass low Frequency point
For 50Hz output frequency models:
45-49Hz: setting the frequency low loss point from 45Hz to 49HZ(Default: 47.0Hz)
For 60Hz output frequency models:
55-59Hz: setting the frequency low loss point from 55Hz to 59Hz(Default: 57.0Hz)
Setting
Parameter 2: Enable or disable programmable outlets.
ENA: Programmable outlets enable
DIS: Programmable outlets disable (Default)
Setting
Parameter 2: Set up backup time limits for programmable outlets.
0-999: setting the backup time limits in minutes from 0-999 for programmable outlets
which connect to non-critical devices on battery mode. (Default: 999)