A B B U P S P R O D U C T S A N D S O L U T I O N S
16: Bypass frequency range setting
Interface
17: Display setting for autonomy time
Interface
18: Acceptable input voltage range setting
Interface
00: Exit setting
Interface
Setting
Parameter 2: Allow or disallow the external output isolation transformer connection.
ENA: If selected, connecting to an external output isolation transformer is allowed.
DIS: If selected, connecting to an external output isolation transformer is not allowed.
(Default)
Setting
Parameter 2: Set up the display setting for autonomy time.
EAT: If EAT is selected, it will display the remaining autonomy time. (Default)
RAT: If RAT is selected, it will show accumulated autonomy time so far.
Setting
Parameter 2: Set the acceptable high voltage point and acceptable low voltage point for
the input voltage range by pressing the Down key or the Up key.
HLS: Input high voltage point
For 100/110/115/120/125 VAC models:
140/145/150: setting the high voltage point in parameter 2. (Default: 150Vac)
LLS: Bypass low voltage point
For 100/110/115/120/125 VAC models:
55/60/65/70/75/80: setting the low voltage point in parameter 2. (Default: 55Vac)
Setting
Exit the setting mode.