Web Connection Setting - Toshiba Smart Manager Engineering Book

Hide thumbs Also See for Smart Manager:
Table of Contents

Advertisement

Smart Manager

5-4. Web connection setting

5-4-1. Displaying and changing
IP address of the Smart
Manager
IP address, subnet mask, default gateway, and
address setting of the Smart Manager can be
displayed and changed using the following
procedures (CODE No. settings).
CODE
Item
No.
IP address
10
(MSB)
11
IP address
12
IP address
IP address
13
(LSB)
Subnet mask
14
(MSB)
15
Subnet mask
16
Subnet mask
Subnet mask
17
(LSB)
Default gateway
18
(MSB)
19
Default gateway
1A
Default gateway
Default gateway
1B
(LSB)
1C
Address setting
Displaying IP address
1
Change the mode to the CODE No. setting
change mode.
Press the
(CHECK),
buttons simultaneously for at least 4 seconds.
(
and CODE No. flash.)
2
Select the CODE No. for IP address.
(1) Change the CODE No. to "10" to "1B" with the
SET TEMP.
(2) The address of each item is displayed as setup
data.
3
Press the
(CHECK) button to finish the IP
address display.
Data
Factory
Setting range
setting
192
0 to 255
168
0 to 255
2
0 to 255
30
0 to 255
255
0 to 255
255
0 to 255
255
0 to 255
0
0 to 255
0
0 to 255
0
0 to 255
0
0 to 255
0
0 to 255
0: Display only
0
1: Manual setting
(CL), and ZONE
or
button.
Changing IP address
The following procedure describes how to change an
IP address using an example of changing IP address to
192.168.2.38.
1
Change the mode to the CODE No. setting
change mode.
Press the
(CHECK),
buttons simultaneously for at least 4 seconds.
(
and CODE No. flash.)
2
Set the data of the CODE No..
(1) Change the CODE No. to "1C" with the SET
TEMP.
or
(2) Change the set data to "1" with the GROUP
or
button.
(
and CODE No. are still flashing.)
(3) Press the
(SET) button to determine the
data. (
lighting.)
(4) Change the CODE No. to "13" with the SET
TEMP.
or
(5) Change the set data to "38" with the GROUP
or
button.
NOTE
At this time, the entered data of the selected CODE No.
has not been saved yet.
3
Exit the CODE No. setting change mode.
Press the
(CHECK) button to write the
updated data in the memory of the Smart
Manager.
When the data has completely been written in the
memory, the CODE No. setting change mode is
exited.
Press the Reset button to restart the Smart
Manager.
4
IP address is set during the restart process.
When the IP address of the Smart Manager has been
changed, be sure to change the IP address of the
client PC to the address in the same segment. Also
change the setting of the browser to the IP address of
the Smart Manager.
Engineering Book
(CL), and ZONE
button.
and CODE No. change to
button.
42
-EN

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents