Specifications Of Energy Monitor Relay Interface (Bms-Ifwh5E); Specifications Of Digital Input/Output Relay Interface (Bms-Ifdd03E) - Toshiba Smart Manager Engineering Book

Hide thumbs Also See for Smart Manager:
Table of Contents

Advertisement

Smart Manager
3-4. Specifications of Energy Monitor Relay Interface
(BMS-IFWH5E)
Power supply
Power consumption
Operating temperature / humidity
Storage temperature
Chassis material
Dimensions
Mass
Power meter input
3-5. Specifications of Digital Input/Output Relay Interface
(BMS-IFDD03E)
Power supply
Power consumption
Operating temperature / humidity
Storage temperature
Chassis material
Dimensions
Mass
Digital input
Digital output
External power supply for Digital Output
-EN
11
220 V - 240 VAC, 50 / 60 Hz
4 W
0 to 40 °C, 10 to 90 % RH
-20 to +60 °C
Galvanized sheet metal 0.8t
66(H) x 193(W) x 246(D) mm
1.35 kg
Input type
Input points
Input resistance
Input "ON" current
Input pulse condition
220 - 240 VAC, 50 / 60 Hz
5 W
0 to 40 °C, 10 to 90 % RH
-20 to +60 °C
Galvanized sheet metal 0.8t (no coating)
66(H) x 193(W) x 246(D) mm
1.35 kg
Input type
Input points
Input resistance
Input "ON" current
Output type
Output points
Output current
Output voltage
Engineering Book
Photo-coupler insulation
8 points
3 k ohm
3.6 mA
50msec or more
Photo-coupler insulation
8 points
3k ohm
3.6 mA
Open collector
4 points
Max. 35 mA (per point)
Less than DC 24 V
DC 12 V, 90 mA

Hide quick links: