Connectable Models / Number Of Units That Can Be Connect - Toshiba Smart Manager Engineering Book

Hide thumbs Also See for Smart Manager:
Table of Contents

Advertisement

Smart Manager

3-6. Connectable models / number of units that can be connect

SMMS-i, SMMS, SHRM, Mini-SMMS
VRF system
Connected unit
1
Outdoor unit (Header)
2
Outdoor unit (Follower)
Indoor unit
4
Indoor group operation
5
Central control device
(*)
Digital Inverter
/ Super Digital Inverter
Connected unit
1
Indoor unit
2
Indoor group operation
3
Central control device
(*)
(*)
VRF / DI
/ SDI
mixed
Connected unit
1
Outdoor unit (VRF series Header)
2
Outdoor unit (VRF series Follower)
3
Indoor unit
4
Indoor group operation
5
Central control device
* The TCC-LINK adapter (TCB-PCNT30TLE2) is required for connection.
Maximum number of
connected units
Up to 16 (Header) units can be connected in one line (TCC-
32
LINK)
3
In the same refrigerant line
• Up to 64 units for group operation (including the follower
unit)
128
• Up to 48 units can be connected in one refrigerant line
• The general-purpose device control interface is regarded as
an indoor unit.
8
20
Up to 10 units can be connected in one line (TCC-LINK)
(*)
(In central control)
Maximum number of
connected units
• Up to 64 units can be connected in one line (TCC-LINK)
• The group follower or twin / triple Double Twin follower unit
is not included. (Up to 512×2 units can be central-controlled
128
during group operation.)
• The general-purpose device control interface is regarded as
an indoor unit.
8
20
Up to 10 units can be connected in one line (TCC-LINK)
Maximum number of
connected units
32
Up to 16 units can be connected in one line (TCC-LINK)
3
In the same refrigerant line
• Up to 64 units can be connected in one line (TCC-LINK)
• It is the total number of the VRF, DI and SDI type indoor
units.
* The group follower or twin/triple double twin follower
128
* The group follower unit is included in the case of VRF
* Up to 48 units can be connected in one refrigerant line
• The general-purpose device control interface is regarded as
an indoor unit.
8
20
Up to 10 units can be connected in one line (TCC-LINK)
Note
Note
Note
unit is not included in the case of DI / SDI series.
series.
in the case of VRF series.
Engineering Book