Length of stripped power cable
35
55
Attach a round pressure terminal to
the end of each wire of the power
cable, communication cable and
power cable for central controller.
Round pressure
terminal
Connections to external equipment
Example of connection to external equipment which is connected to Digital Input/Output connector.
Input /
Designation
Output
item
DO1
(Alarm output)
DO2
Status
(Run output)
output
DO-COM
(Output
common)
DI1
(All stop input)
DI2
(All start input)
Control
DI3
input
(Fire alarm
input)
DI-COM
(Input
common)
Length of stripped TCC-LINK
communication cable
35
L
N
Attach the supplied clamp filter to the LAN cable.
* Wind the LAN cable around the clamp filter as shown
below when attaching the filter to the cable. After
attaching the filter, fix it to the LAN cable using a
supplied cable tie.
* Attach the clamp filter as near the main unit as possible.
LAN cable
Central Controller side
Input / output
conditions
Allowable
terminal voltage
/ current
DC24 V / 35 mA
Non-voltage A
contacts
Pulse or static
* Non-voltage
contacts must
be compatible
with minimal
current.
DC5 V / 3 mA
Length of stripped RS-485
communication cable
35
55
External equipment side
Terminal name
DO1
DO2
DO-COM
5V
DI1
5V
DI2
5V
DI3
DI-COM
Engineering Book
Length of stripped Digital Input/
Output communication wire
Loosen the screw with the screw
driver, insert the Digital Input/Output
communication wire, then tighten
the screw again to fix the wire firmly.
Example of circuit
Digital
Wiring length:
output
100 m or less
Pulse or static
Pulse or static
Pulse width:
300 ms or more
Wiring length:
Static
100 m or less
35
6
Input / output
conditions
20
-EN