Test Run; Test Run From Smart Manager; Test Run From Web Browser - Toshiba Smart Manager Engineering Book

Hide thumbs Also See for Smart Manager:
Table of Contents

Advertisement

Smart Manager
7

Test run

7-1. Test Run from Smart
Manager
<Conducting a Test Run for the Smart
Manager>
1
Turn on the power of all connected air
conditioners.
2
Turn on the power of the Smart Manager.
3
Make sure that the number of air
conditioners connected to each line (only
Header units when group control is
performed) equals the group number count
displayed on the Smart Manager.
4
When these numbers are identical, there is
no problem.
If they differ, set central control addresses again
according to "Central Control Address (Group
Number) Setting." Also make sure that there is no
incorrect wiring.
5
Check if the target indoor units can be
operated from Smart Manager.
6
If the target indoor unit does not run, check
the central address.
7-2. Test Run from Web
Browser
Before test run from the Web browser, it is required to
create data to be displayed on the Web browser with
Setting File Creation Software and upload it to Smart
Manager.
For details, refer to the operation manual of Setting File
Creation Software.
1
Turn on all the air conditioners.
2
Turn on Smart Manager.
3
Set the IP address of Smart Manager. (*1)
4
Connect Smart Manager to a computer via
LAN cable. (*2)
5
Start the Web browser and enter the URL of
the target language. The IP addresses in the
following URLs are the factory settings. If
the IP address has been changed with Smart
Manager, enter the new address.
English http://192.168.2.30/en/index.html
German http://192.168.2.30/de/index.html
Italian http://192.168.2.30/it/index.html
French http://192.168.2.30/fr/index.html
Spanish http://192.168.2.30/es/index.html
Chinese http://192.168.2.30/cn/index.html
6
When the log in screen appears, proceed to
Step 8. If not, proceed to Step 7.
7
Check the URL. Also check the proxy setting
of the Web browser. (*1)
8
Log in with User name: TCC, Password:
TCC.
9
Confirm that the registered "Floor",
"Tenant", "Area", and air conditioner name
are correct.
10
Confirm that the information on the
registered ones is displayed.
11
Check if the air conditioners displayed on
the Web browser run properly.
12
If the target indoor unit does not run, re-
check the line address of the indoor unit,
indoor unit address, and group address.
*1For details, refer to Network Configuration Guide.
*2To use the HUB, use the straight cable. To establish
one-to-one direct connection, use the cross cable.
Engineering Book
54
-EN

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents