Specifications - Toshiba LONWORKS LIU007Z Instruction Manual

Communication option for tosvert vf-fs1 series
Table of Contents

Advertisement

5. Specifications

< Environmental specification >
Item
Service environment
Operation temperature
Storage temperature
Relative humidity
Vibration
< L
W
communication option (LIU007Z) side >
ON
ORKS
Item
Applicable
model
Commun
Communication
ication
between
method
inverter
Baud rate
Parity
Control power supply
Logic input terminal
Logic output terminal
Relay contact output
terminal
Analog input terminals
Analog output terminals
Power supply output
< Network side >
Item
Transceiver
Channel type
Communication signal
Transmission distance
(Free topology)
Transmission distance
(Bus topology)
Number of connected
nodes
Protocol
Address and related
items
Network variables
Service pin
Terminal block
Conforms to VF-FS1
Conforms to VF-FS1
-25 to +65℃
20 to 93% (free from condensation and vapor)
2
5.9m/s
(0.6G) or less (10 to 55 Hz) (To be complied with JIS C0040.)
Specification
VF-FS1
MODBUS-RTU
19200bps
Even number
5 V
DC
2 circuits (F,R)
Slide switch (SW1) enable to select
logical configurations (Source/Sink).
Nothing
1 circuit (FL): 30V -0.5A
DC
250V -1A (cosφ =1)
AC
250V -0.5A (cosφ =0.4)
AC
1 circuit (VIB):
10V
30kohm)
Nothing
24V -50mA
DC
Specification
TP/FT-10 type
(Free topology transceiver
2 wires plus shield
Between devices: 400m at maximum
Total cable length: 500m at maximum Level 4/22AWG
Total cable length: 1400m at
maximum
Stub length: 3m at maximum
Free topology 63 nodes at maximum
LonTalk
Number of domains: 2
Number of address entries: 37
Number of alias tables: 8
Number of transmission data: 17
Number of receiving data: 8
Number of configuration property: 12
Mechanical switch (SW2)
Detachable terminal block 3-pole
- 13 -
Specification
Only one board connection is
available.
Set the inverter parameter
(refer to section 3.2)
Supplied from inverter
Not isolated
Isolated
(R
=
DC
IN
Not isolated
Current limit function
78kbps
ANSI/EIA/CEA 709.3
NETA, SHLD, NETB
When recommended cable is used:
When recommended cable is used:
Level 4/22AWG
Because a host and routers are
counted as one board, the option can
be connected up to 63 nodes.
ANSI/EIA 709.1
L
M
ON
ARK
Drive functional profile.
Used for notification of Neuron ID to
the host.
Applicable terminal block
Manufacturer: PHOENIX CONTACT
Type-Form : MSTB 2,5/3-ST-5.08
E6581371
Note
Notes