4.2.3 Conditions when setting the motor protection
4.2.4 Setting of the motor protection
Ensure that the following conditions are met when setting the motor protec-
tion or when displaying the set value:
•
The device is supplied with voltage.
•
There are no errors.
•
There is no start signal on the terminals ON, L or R.
Activating parameterization mode
▶
Press the RESET button for at least 6 seconds.
→ The green PWR LED flashes once.
Press 6 sec
Setting the motor rated current
▶
Turn the potentiometer to the desired value.
I
e
Checking the value on the LEDs
Compare the set value with that which is displayed on the
▶
LEDs (→ table 10, page 30).
or QR code
Leaving parameterization mode
▶
Press the RESET button.
Press > 1 sec
EMS2... Electronic motor starter 10/19 MN034003EN www.eaton.com
4 Short-circuit / motor protection
4.2 Motor protection
29