4.2.6 Tripping and reset

Tripping
In the case of tripping,
the motor starter switches off,
the output relay switches
(connection between terminals 95 and 98 instead of between terminals
95 and 96)
the LED ERR flashes,
and one of the LEDs L, R or ON
lights up (depending on the previously driven operating direction).
Reset
EMS2 series motor starters have a "thermal memory", which means that a
reset after the motor protection has tripped is possible only once a waiting
period (cooling-down time) has passed.
After the waiting period has passed, the L, R or ON LED which had previ-
ously lit up permanently prior to the error flashes (see also → section 6.3,
"Resetting after an error message", page 42).
Figure 17:Front view
EMS2... Electronic motor starter 10/19 MN034003EN www.eaton.com
4 Short-circuit / motor protection
4.2 Motor protection