5.2 Reversing starter 24 V DC with safety function (dual-channel) (cat. 3, SIL 3, PL e)
24 V DC
F1
1/
3/
5/
L1
L2
L3
EMS2-ROS-...
2/
4/
6/
T1
T2
T3
95 96 98
U1
V1
W1
M
3 ~
Figure 21: Reversing starter with safety function (dual-channel)
In this example (shown in figure 21), the EMS2-ROS... motor starter is used
in combination with an ESR5 series safety relay. The preset for the control
commands for the operating direction takes place directly at 24 V DC on the
L or R terminal.
In contrast to the previous example, in the case of a controlled stop, the
supply voltage on the terminals A1 and A2 is switched off by the safety relay,
which causes a reduction in the lifespan of the motor starter.
Please also note the information about the lifespan of devices on Page 33.
EMS2... Electronic motor starter 10/19 MN034003EN www.eaton.com