Example
A motor with the values shown below is to be operated with an EMS2 elec-
tronic motor starter.
Motor:
Power:
Rated operational current I
at 400 V:
Startup factor I
Control panel
temperature:
Questions:
Is operation possible?
How should the motor starter be mounted?
Checks:
Step 1:
Check to see if the motor starter is suitable for the maximum current (56 A).
I
= I
x startup factor = 4,7 A x 8.5 = 39.95 A < 56 A
max
Mot
Step 2:
Which motor current is permissible at an ambient temperature of 55 °C?
(→ Figure 12)
directly linked: 3 A < 4.7 A → not permissible!
at a 20 mm distance: 6.7 A > 4.7 A → permissible!
Conclusion:
The motor starter EMS2 can be used for this application; it must, however,
be mounted with at least 20 mm distance between the next device.
EMS2... Electronic motor starter 10/19 MN034003EN www.eaton.com
3 Plug-in motor starter ROSF for mounting on an adapter
3.2 Layout of devices with adapter EMS2-XTH
/ I
:
max
Mot
P
= 2.2 kW
Mot
e
I
= 4.7 A
Mot
8.5
55 °C
23