Eaton EMS2 Series Manual page 45

Electronic motor starter
Hide thumbs Also See for EMS2 Series:
Table of Contents

Advertisement

LED
PWR
ERR
L / (–)
R / (ON)
Table 11:
Status messages – combination of four LEDs
Status
Off
Ready for operation
Drive switched on
Drive switched on
Internal error
Motor protection tripped during
counterclockwise operation
→ section 4.2, "Motor protec-
tion", page 27
Motor protection tripped during
counterclockwise operation
→ section 4.2, "Motor protec-
tion", page 27
Motor protection tripped during
clockwise operation
→ section 4.2, "Motor protec-
tion", page 27
Motor protection tripped during
clockwise operation
→ section 4.2, "Motor protec-
tion", page 27
Bad checksum
Asymmetrical phase current
Motor is stalled
(counterclockwise operation)
Motor is stalled
(clockwise operation)
• Phase failure
• No motor connected
• Motor current < I
for longer
min
than 2 s
• Phase failure
• No motor connected
• Motor current < I
for more
min
than 2 s
EMS2... Electronic motor starter 10/19 MN034003EN www.eaton.com
6.1 LEDs on the front of the device
Description
No control voltage U
present
S
Control voltage U
present
S
Counterclockwise operation (L)
Clockwise operation (R or ON)
Device needs to be replaced
Motor protection in cooling-down
phase,
reset not possible.
Cooling-down phase concluded,
manual reset possible
Motor protection in cooling-down
phase,
Reset not possible.
Cooling-down phase concluded,
manual reset possible
Error during system recovery. The ther-
mal memory of the motor protection
function is set to the maximum value.
The error must be manually acknowl-
edged in automatic mode.
The currents in the phases deviate
from one another by more than 33%.
The maximum measurable motor
current is exceeded for longer than 2 s.
The maximum measurable motor
current is exceeded for longer than 2 s.
Error has occurred during counter-
clockwise operation. The power circuit
is still connected.
Error has occurred during clockwise
operation. The power circuit is still
connected.
6 Status messages
Reset
Not possible
Manually after a cooling-down time
of approx. 2 min;
automatically after approx. 20 min
with a bridge between AUT and RES
Manually after a cooling-down time
of approx. 2 min;
automatically after approx. 20 min
with a bridge between AUT and RES
Manually after a cooling-down time
of approx. 2 min;
automatically after approx. 20 min
with a bridge between AUT and RES
Manually after a cooling-down time
of approx. 2 min;
automatically after approx. 20 min
with a bridge between AUT and RES
Manual
Manual
Manual
Manual
Automatic, as soon as the error has
been remedied
Automatic, as soon as the error has
been remedied
41