4.2 Motor protection
Themotor protection prevents the connected motor from heating up too
much if the actual motor current is greater than the specified rated current
(i. e. I > I
). The time up until tripping depends on the current and the trip
n
class.
Devices with a rated operational current I
t [s]
1000
600
400
300
200
100
60
40
30
20
10
6
4
3
2
1
0.6
0.4
0.3
0.2
0
1
2
3
Figure 15: Tripping characteristics class 10
t = tripping time
I = actual motor current
I
= setting of the motor protection on the EMS2 device
n
Devices with a rated operational current I
t [s]
1000
600
400
300
200
100
60
40
30
20
10
6
4
3
2
1
0.6
0.4
0.3
0.2
0
1
2
3
Figure 16: Tripping characteristics class 10A
t = tripping time
I = actual motor current
I
= setting of the motor protection on the device EMS2
n
EMS2... Electronic motor starter 10/19 MN034003EN www.eaton.com
of 2.4 A or 3 A are in trip class 10.
e
4
5
6
7
of 9 A have the tripping class 10A.
e
4
5
6
7
4 Short-circuit / motor protection
4.2 Motor protection
Class 10
8
9
10 I / I
n
Class 10 A
8
9
10 I / I
n
27