0x1C
●
0x1D
●
0x1E
●
...
10.3 Errors in the expansion functions (from 0x40 to 0x9F)
0x40
0x41
0x42
0x43
0x44
0x45
●
0x46
0x47
●
0x48
0x49
0x4A
0x4B
0x4C
0x4D
0x4E
0x4F
0x50
●
0x51
0x52
0x53
0x54
●
ERROR_SYNCHRONISATION_DURING_
INITIALISATION
ERROR_PROCESSOR MALFUNCTION
ERROR_STATE BLOCK_SFR REGISTER
Free
ERROR_FAN RATED VALUE PRESETTING
ERROR_FAN_DEVIATION
ERROR_FAN_NO_RESPONSE
ERROR_IONISATION INPUT_TEST
ERROR_CURVE CRC16_TEST
E R R O R _ M O D U L A T I O N
PRESETTING_NOT VALID
Free
ERROR_STEP MOTOR TYPE_NOT VALID
ERROR_TOLERANCE ExCEEDED_STEP
MOTOR
ERROR_REFERENCE NOT FOUND_STEP
MOTOR
ERROR_NO_REACTION_STEP MOTOR
ERROR_PARAMETERS SET STICK_NOT
FOUND
E R R O R _ PA R A M E T E R S S E T S T I C K _
ALIGNMENT BLOCK
ERROR_PARAMETERS SET STICK_WRONG
PASSWORD
ERROR_PARAMETERS SET STICK_NO_
CONTINUOUS OPERATION
ERROR_PARAMETERS SET STICK_STICK_
TYPE
ERROR_WRONG_SUPPL V_RESPONSE
ERROR_SUPPL V_DELAY_NOT VALID
Free
ERROR_LACK OF GAS_GDWVPS
ERROR_PWM_CALIBRATION VALUES
0006081265_201212
? The MPA is subject to strong EMC interferences
? In the curve segment a fan rated value has been preset that
is lower than the minimum rpm value or higher than the fan
maximum rpm value (P26 or P27). For example: P26 (minimum
rmp value) could be set to 500 rpm, while the number of revs for
the modulation degree is pre-set to 480 rpm. Or P27 (maximum
rpm value) is set to 5600 rpm, while pre-ventilation B has to be
performed at 5800 rpm.
? The number of pulses of the fan response is improperly set
? The fan is not suitable for the required number of revs
? The pre-set tolerance is too low or the fan regulator is not
optimised
? The fan response line has not been connected properly or
it is interrupted
? The fan is blocked and does not turn
? The fan receives no current or it is faulty
? The curve segment has been temporarily modified (for ex. for
the first commissioning), but then it has been properly enabled
D E G R E E
? The cables to the step motor are not properly connected or
are partly interrupted
? The step motor has a torque that is higher than the one
permitted, for example due to an improper installation of the
cover or to pressure drops.
? see error 0x48
? see error 0x48
? Parameters set activated but not entered into the MPA
? Faulty stick
? The duration of the adjustment operation (P70) takes more
than 23 h and 59 min and continuous operation has not been
activated
? The PWM output have been set to analog operation (0..10 V
or 4...20 mA), but the appropriate stick has not been inserted.
? A parameter could not be transferred from the stick, for
example because the MPA variables limits have been reduced
? The entered password is not valid for this stick
? The duration of the adjustment operation (P70) takes more
than 23 h and 59 min and continuous operation has not been
activated
? The stick is not suitable for this type of automatic device
? The parameters P25 or P53 have been set to a non permitted
value, since the status (P50 or P51) cannot last so long
? During the programming of the parameters set stick, the
EEPROM has been modified or deleted
? Parameters set stick faulty
22 / 30