Measures in the Event of
Emergency

Emergency Stop Procedure

Thoroughly understand the stopping procedure to
be followed in the event of emergency.
Use the emergency stopping devices
1
of the generator
Stopping Devices Installed During
Manufacturing the Generator" (→
Page
64).
If the engine will not stop, pull the
2
manual stop lever of this engine in
the direction of stopping and hold
this position.

Fig. 1-9 Emergency Stop Procedure

• The location of the manual stop lever
varies depending on the specification
of the engine. Refer to
System - Location" (→ Page
After the engine has stopped
3
completely, release the manual stop
lever.
When stopping the engine by pulling
the manual stop lever, keep pulling
the lever until the engine stops
completely.
* Otherwise, the engine may start again.
If the stop switch of the generator will
not function and the engine will not
stop by using the manual stop lever,
shut off fuel supply.
* Otherwise, the extent of damage may increase.
Mitsubishi Diesel Engine S16R & S16R2 OPERATION & MAINTENANCE MANUAL
Pub. No. K29001-00320 Revision: 1
"Emergency
"Protection
82).