Table 7-2 SME Generator Use Diesel Engine Rating Definition (2/2)

Symbol
Name of rating
Overload operation (Rack set)
Definition
Ave. load factor/24 Hr
Ave. load factor/yr
Operating Hr/yr (*4)
Top
Major
Application
*1: This condition constitutes a part of required conditions for warranty that Shanghai MHI Engine co., Ltd. (hereinafter "SME") agrees
with the other party under Diesel Engine Sales Contract with the party (hereinafter "Individual Contract"), however details of the
warranty descriptions and the conditions shall be referred to the Individual Contract.
Atmospheric condition as per ISO 15550:2002 (JIS B 8003:2005) (Barometic pressure:100 kPa, ambient temperature:298 K,
relative humidity:30%).
*2: Average load factor (per day or year) shall be calculated as per the formula in ISO 8528:2005 'average power output (Ppp)'.
*3: Refer to Operation Manual for more information regarding inspection and maintenance including items and descriptions.
*4: Warranty aren't valid after Major Overhaul.
*5: For backup or emergency purpose engine, it is needed to have output margin of 5% or more for the customer demand output to
avoid engine stall by output tolerance (ISO 15550) and frequency variation etc.
*6: Although power is same as Prime rating, but DCC don't have overload. This point is influenced to step load performance. Then,
engine generator set manufacturer is required to check performance of the DCC rating engine.
*7: UPTIME compliant: This DCC rating meets the requirement of a Tier III and IV data center site with no runtime limitation when the
operation is loaded to 'N' demand for the engine generator set.
This document may be changed without prior notification.
Mitsubishi Diesel Engine S16R & S16R2 OPERATION & MAINTENANCE MANUAL
Pub. No. K29001-00320 Revision: 1
DCC
C
Data center Continuous
Continuous
(*7)
Not possible (P) (*5, *6)
Not possible (C)
Rating that can continuously generate power without
For generator in Data
limitation for operating hour per year under the re-
center application (where
quired conditions for warranty in this document.
reliable grid is available)
COP as specified in ISO 8528:2005.
100% load is allowed in
100% or lower
case of grid failure
75% or lower
100% or lower
Unlimited
Unlimited
6000Hr or 4yr whichever
2000Hr or 4yr whichever
comes earlier
comes earlier
(Recommended: 4000Hr)
12000Hr or 8yr whichever
4000Hr or 8yr whichever
comes earlier
comes earlier
(Recommended: 8000Hr)
Data center
Base load, cogeneration system
7 SCHEDULED MAINTENANCE
D
Not possible (D)
In addition to the defini-
tion for C above, this rat-
ing shall be used 90% or
higher average load fac-
tor or longer maintenance
interval are required.
90% or lower
100% or lower
90% or lower
100% or lower
Unlimited
Unlimited
8000Hr or 4yr whichever
8000Hr or 4yr whichever
comes earlier
comes earlier
(Recommended: 6000Hr)
(Recommended: 6000Hr)
16000Hr or 8yr whichever
16000Hr or 8yr whichever
comes earlier
comes earlier
(Recommended:
(Recommended:
12000Hr)
12000Hr)
121