Ups Cable Connection Reference - Huawei UPS5000-E Series User Manual

Integrated ups 3.0
Hide thumbs Also See for UPS5000-E Series:
Table of Contents

Advertisement

UPS5000-E-(60 kVA-125 kVA)
User Manual (Integrated UPS 3.0)
Install a battery rack and batteries. For details, see the battery installation guide delivered
along with the batteries.
Installing Lithium Batteries
For details, see the SmartLi user manual.

3.2.4 UPS Cable Connection Reference

Context
Procedure
Step 1 Route a cable into the cabinet and bind it to a nearby beam.
Step 2 Pull the cable to the copper bar to which the cable is to be connected, determine the cable
length, and mark the cable at the position where the cable is to be cut.
Step 3 Pull the marked cable out of the cabinet, cut the cable from the marked position, strip the
cable, and crimp a terminal.
Issue 01 (2020-04-13)
Before installing batteries, read through the battery safety precautions and install batteries
as instructed in the delivered battery installation guide.
Install the batteries from the lower layer to the upper layer to ensure the system is secure
and balanced.
Keep away from cabinets when preparing cables to prevent cable scraps from entering the
cabinets. Cable scraps may cause ignition during power-on and result in personal injury
and device damage.
After installing cables, clean the cabinet top, bottom, copper bar wiring positions, and
other positions. Ensure that there is no dust or scraps inside and around cabinets.
Prepare terminals onsite. The length of the copper wire should be the same as that of the
part of the terminal that covers the conductor.