Huawei UPS5000-E Series User Manual page 123

Integrated ups 3.0
Hide thumbs Also See for UPS5000-E Series:
Table of Contents

Advertisement

UPS5000-E-(60 kVA-125 kVA)
User Manual (Integrated UPS 3.0)
Item
Altitude (m)
Top outlet fan
Air filter
maintenance
period (d)
Intra-rack
power module
start delay (s)
Inter-rack
power module
start delay (s)
Batt. temp.
sensor
[B_TEMP]
BCB trips if
UPS stops
power supply
Issue 01 (2020-04-13)
Description
operations under the guidance
of maintenance engineers.)
NOTE
Ensure that the BSC signal cable
between the BSC master and slave
systems is properly connected and
that BSC-related hardware is
properly installed.
Set this parameter based on the
altitude of the place where the
rack is used.
Enable this parameter if a top
outlet fan is configured. Then the
fan running status can be
checked.
Specifies the rack air filter
maintenance interval. If it is set
to 0, there is no reminder.
These two parameters enable the
UPS to control the interval that
each rack (or module) transfers
from battery mode to normal
mode, which reduces the impact
on the generator or power grid. In
the case of battery undervoltage,
the system automatically shortens
the delay for transferring to
normal mode to 1/8 of the normal
delay to accelerate the transfer
and prevent battery
overdischarge. The start delay of
a module in a rack varies
depending on the rack number
and module number. #1 module
in rack 1 does not have a start
delay.
The short-distance battery
temperature sensor monitors the
ambient temperature near
batteries, and ensures that
batteries work reliably and
securely.
Indicates whether the BCB trips
when the system stops supplying
power and the output power is
off.
Copyright © Huawei Technologies Co., Ltd.
4 LCD Interface
Default Value
Value Range
≤ 1000
≤ 1000,
1000–2000,
2000–3000,
3000–4000,
4000–5000
Disable
Disable, Enable
0
0–365
The default
0.5–120.0
value of this
parameter
depends on the
default number
of power
modules. The
default value is
2.0, 1.0, and 0.5
for 1–5, 6–10,
and 10–20
power modules
respectively.
5
2–120
Disable
Disable, Enable
Enable
Disable, Enable
115