UPS5000-E-(60 kVA-125 kVA)
User Manual (Integrated UPS 3.0)
Before connecting cables, check that all UPS input switches are OFF.
Prepare terminals onsite. The length of the copper wire should be the same as that of the
part of the terminal that covers the conductor.
Figure 3-24 Connecting a ground cable
Step 4 Connect a ground cable to the safety ground of the UPS cabinet.
Figure 3-25 Connect a ground cable to the safety ground of the UPS cabinet
Step 5 Connect AC input power cables.
Issue 01 (2020-04-13)
MCCB cabinet input:
a.
Connect AC input power cables to input terminals L1, L2, L3, and N on the UPS
cabinet.
Copyright © Huawei Technologies Co., Ltd.
3 Installation
76