UPS5000-E-(60 kVA-125 kVA)
User Manual (Integrated UPS 3.0)

3.1.2.2 Installation Environment

3.1.2.3 Installation Clearances

Reserve sufficient space around the cabinet for operation and ventilation:
Figure 3-2 Reserved clearances (unit: mm)

3.1.3 Preparing Power Cables

Issue 01 (2020-04-13)
Do not install the UPS in high temperature, low temperature, or damp environments.
Install the UPS away from water sources, heat sources, and flammable or explosive
materials. Keep the UPS away from direct sunlight, dust, volatile gases, corrosive
materials, and air dense with salt particles.
Do not install the UPS in environments with conductive metal scraps in the air.
The optimal operating temperatures for valve-regulated lead-acid batteries (VRLA
batteries) are 20–30° C. Operating temperatures higher than 30° C shorten the battery
lifespan and operating temperatures lower than 20° C reduce the battery backup time.
Reserve a clearance of at least 800 mm from the front of the cabinet.
Reserve a clearance of at least 800 mm from the rear of the cabinet.
Reserve a clearance of at least 500 mm from the top of the cabinet.