UPS5000-E-(60 kVA-125 kVA)
User Manual (Integrated UPS 3.0)
Item
Minimum
bypass voltage
Bypass
frequency
range (Hz)
Battery Settings
Battery parameter settings impact battery maintenance, battery lifespan, and UPS discharge
time. When you set battery parameters, note the following:
Issue 01 (2020-04-13)
Description
bypass voltage is not normal and
that the bypass is unavailable.
When the difference between the
bypass voltage and the rated
voltage exceeds the upper
threshold for the bypass voltage,
the system determines that the
bypass voltage is not normal and
that the bypass is unavailable.
When the difference between the
bypass input frequency and the
rated frequency is greater than
the specified value, the system
determines that the bypass
frequency is abnormal, so the
bypass is unavailable.
Copyright © Huawei Technologies Co., Ltd.
4 LCD Interface
Default Value
Value Range
the value range is +10%, +15%,
and +20%. The default value is
+15%.
When the voltage level is 415 V,
the value range is +10% and
+15%. The default value is
+10%.
–20%
–10%, –15%,
–20%, –30%,
–40%, –50%,
–60%
± 2 Hz
± 0.5 Hz to ± 6
Hz
119