UPS5000-E-(60 kVA-125 kVA)
User Manual (Integrated UPS 3.0)
No.
05
06
07
08
09
10
11
12
13
14
15
Issue 01 (2020-04-13)
Item
Cable labels
Ground cable connections
Distances between cable ties
Cable connections
Live wire and neutral wire
connections
Input and output live wire phase
sequences
Battery cable connection
Operating environment
Copper busbar short circuit
Surge protection switch state
Foreign matter cleaning inside
the cabinet
Copyright © Huawei Technologies Co., Ltd.
Expected Result
Both ends of each cable are labeled. Labels
are easy to understand.
The ground cable is securely connected to the
equipment room ground bar. Measure the
resistance between the UPS ground cable and
the equipment room ground bar, which must
be less than 0.1 ohm.
Distances (recommended: 30 cm) between
cable ties are the same, and no burr exists.
Cables are properly connected according to
wiring diagrams.
The connections are correct. Connect the input
1L1, 1L2, 1L3, 1N, 2L1, 2L2, 2L3, and 2N
wires correctly. Connect the primary and
secondary ATS power cables correctly
In single UPS mode, mains and bypass input
and output live wires are connected in a
correct sequence.
Check that the voltages on the positive and
negative battery terminals and battery N are
correct using a multimeter.
Clean the conductive air and other sundries.
Check that copper busbars are open-circuited
using a multimeter or an insulation resistance
tester.
The surge protection switch is turned on.
The inside and outside of the cabinet, and
other operating components, are free from
conductive dust.
1. There is no foreign matter (such as copper
wires and screws) on the top of the cabinet.
2. There is no foreign matter on the copper
bar terminals.
3. There is no foreign matter around switch
terminals.
4. There is no foreign matter on the bottom
plate of the cabinet.
5. There is no foreign matter on the rear
module subrack.