Auto Update Mode - Mitsubishi Electric Melsec WS Series User Manual

Safety controller ethernet interface module
Hide thumbs Also See for Melsec WS Series:
Table of Contents

Advertisement

MELSEC-WS
127
8.4.4

Auto update mode

This section describes an example of communications in auto update mode.
The QSCPU reads MELSEC-WS safety controller information (e.g. logic result,
CRC, and each module status) from the safety controller through communications
between the WS0-GETH and the QJ71E71-100. The WS0-GETH automatically
sends input data sets to the QJ71E71-100 at 5000-ms intervals.
Read-target data
Logic result 0 (input data set 1)
CRC (input data set 2)
Each module status (input data set 3)
Figure 71: System configuration example
(1) Parameter configuration
(a) Configuration required for the WS0-GETH
Configuration examples of network parameters required for communications in
auto update mode are shown below. Configure these parameters using Setting
and Monitoring Tool.
The WS0-GETH requires no program for communications.
1) Creating a hardware configuration
Refer to Section 8.2.2 (1).
2) Assigning an IP address
Refer to Section 8.2.2 (1).
3) Configuring TCP/IP
Refer to Section 8.2.4 (1).
4) Editing data sets
Refer to Section 8.2.2 (1).
Procedures before operation

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec ws0-geth0020

Table of Contents