Line Power Supply 3X200-240 V Ac - Danfoss VLT FC 102 Instruction Manual

Hvac drive
Hide thumbs Also See for VLT FC 102:
Table of Contents

Advertisement

Specifications
8.1.1 Line Power Supply 3x200–240 V AC
Type Designation
Typical Shaft Output [kW]
Typical Shaft Output [HP] at 208 V
6)
IP20/Chassis
IP55/Type 12
IP66/NEMA 4X
Output current
Continuous (3x200–240 V) [A]
Intermittent (3x200–240 V) [A]
Continuous kVA (208 V AC) [kVA]
Max. input current
Continuous (3x200–240 V) [A]
Intermittent (3x200–240 V) [A]
Additional specifications
Estimated power loss at rated max. load [W] 4)
IP20, IP21 max. cable cross-section (line power, motor, brake and load
2
sharing) [mm
/(AWG)]
IP55, IP66 max. cable cross-section (line power, motor, brake and load
sharing) [mm
2
/(AWG)]
Max. cable cross-section with disconnect
3)
Efficiency
Table 8.2 Line Power Supply 3x200–240 V AC - Normal overload 110% for 1 minute, P1K1-P3K7
®
VLT
HVAC Drive Instruction Manual
P1K1
1.1
1.5
A2
A4/A5
A4/A5
6.6
7.3
2.38
5.9
6.5
63
0.96
MG11AJ22 - Rev. 2013-09-13
P1K5
P2K2
P3K0
1.5
2.2
3.0
2.0
2.9
4.0
A2
A2
A3
A4/A5
A4/A5
A5
A4/A5
A4/A5
A5
7.5
10.6
12.5
8.3
11.7
13.8
2.70
3.82
4.50
6.8
9.5
11.3
7.5
10.5
12.4
82
116
155
4, 4, 4 (12, 12, 12)
(min. 0.2 (24))
4, 4, 4 (12, 12, 12)
6, 4, 4 (10, 12, 12)
0.96
0.96
0.96
P3K7
3.7
4.9
A3
A5
A5
16.7
18.4
6.00
15.0
16.5
8
8
185
0.96
53

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents